Honeywell DT90e Wired Digital Room Thermostat
Replaces Obsolete DT200 (T6620B1008)
The DT90E digital room thermostat has been designed to provide automatic temperature control of gas or oil fired boiler systems underfloor heating electric heating and zoning systems. Energy efficiency is addressed by state of the art control performance qualifying it as a Load Compensator. The DT90E has an ECO button energy saving feature which gives timed setback or boosts temperatures to reduce energy demand. This is a TPI (Time Proportional Integral) control product as defined in the Building Regulations which make boilers operate more efficiently and provide close accurate control. The ‘OFF’ setting can be used for frost or hypothermia protection assuming the system time control is also switched on. 'Installer Mode' allows control to be matched to the system and user requirements adapting minimum on or off times set point controls etc. Two wire volt free connections are ideal for use with combination boilers or heating zones.
* Features:
* Energy saving TPI control
* ECO button for energy saving mode
* Simple user operation
* 5 to 35°C set point range
* 'OFF' setting with adjustable OFF setpoint
* Direct replacement of the DT200 digital thermostat
* Mains or low voltage switching
* Two wire connection
* 8(3)Amp contacts
* Dimensions: 90x92x27mm
Please Note: When replacing a traditional thermostat with a digital thermostat it is important that any neutral wire is safely isolated and NOT connected the the digital thermostat.
Ask a Question about Honeywell DT90e Wired Digital Room Thermostat
-
You can place each wire in a terminal strip with nothing the other side. Then wrap in electrical tape.
-
Hi.
Yes it will. Red to A, yellow to B.
The blue should be isolated and not connected to the DT90e.
-
Hi. Yes, it will connect to the same 2 wires.
-
It sounds like the TPI feature. It is a fuel saving feature and is best left alone unless there is temperature discomfort.
-
No, the DT90E does not have a backlight feature.
-
Hi. As long as it is controlling a gas or oil boiler. The DT90e is not suitable for electrical heating.
-
Yes you could. However these cannot be programmed.
-
Yes. The neutral is not needed, so isolate it.
-
Yes it will. If you have a wire in terminal 2, you will need to isolate it. Wiring as follows: T6360 - DT90e 1 - A 3 - B 4 - C If terminal 4 is empty, leave terminal C empty.
-
Yes. The neutral and earth wires will not be needed by the new thermostat, so must be isolated.
-
This is not wireless and will not talk to a Siemens receiver. I would recommend replacing like-for-like to avoid replacing the receiver.
-
It must have an output on terminal 3 of the T6360B. It is battery powered, so doesn't need the neutral.
-
Yes, you can. The neutral is not needed so must be safely isolated.
-
Yes it can. You will need to isolate the neutral and NOT connect it to the DT90e.